EasyGen 1000 Series

I/Os

  • FlexRangeTM – true RMS 3phase generator and mains voltage, measuring inputs:
    • Rated 120 Vac (max. 150 Vac) and
    • Rated 480 Vac (max. 600 Vac) in 1 unit
  • True rms 3phase generator current/power
  • True rms 1phase current input alternatively and freely configurable for
    • Mains current
    • Ground current (ground fault protection)
  • 1 speed input (magnetic/switching)
  • up to 8 configurable discrete alarm inputs
  • LogicsManagerTM – up to 9 program. relays
  • FlexInTM – 2 configurable analog inputs
  • FlexCANTM – CAN bus communication (32 participants, isolated)

Protection

Generator / Engine: Battery voltage, overspeed (12), over-/undervoltage (59/27), over-/underfrequency (81O/U), overload (32), reverse/reduced power (32R/F), unbalanced load (46), definite time-overcur. (50/51), inverse time-overcurrent (IEC255), calculated + measured ground fault

Features

  • FlexAppTM Technology (4 application modes)
  • DynamicsLCDTM – 128×64 pixel graphical interactive LC display with softkeys
  • Start/stop logic for Diesel/Gas engines
  • Engine pre-glow or purge control
  • kWh meter, kvarh meter
  • Operating hours/start/maintenance counters
  • Configurable trip levels/delays/alarm classes
  • Push-buttons (softkeys) for direct control
  • PC and/or front panel configurable
  • Multi-level password protection
  • Multi-lingual capability (10 languages in 1 unit configurable: English, German, French, Italian, Spanish, Portuguese, Russian, Turkish, Chinese, Japanese)
  • Event recorder (300 events, FIFO) with real time clock (battery backed; min. 6 years)
  • Modem connectivity with DPC
  • easYlite annunciator support via CAN bus
  • Remote control via interface / digital signals

Differentiation

  • Current input as ../5 A (standard) or ../1 A
TOP